FAQs: Military

Question:
How do I perform a Counts Test on the FUELMASTER®

Answer:

PLACE HOSE IN MANUAL POSTION AND DISPENSE EXACT QUANTITY TO DETERMINE IF PULSES ARE BEING RECEIVED OR IF DIVIDE RATIO IS CORRECT

EXAMPLE: HOSE 2 ONE GALLON PUMPED WITH A RESULTING COUNT OF 50 = 50:1 DIVIDE RATIO

SUPERVISOR MENU:                1=SYSTEM<

>A=CONFIG, B=REPORTS, C=HOSES,     D=EXIT<

>CONFIGURATION:  15:07:12  12/31/09  FRI.<

>A=MODIFY, B=TESTS, C=TIME/DATE, D=EXIT  <

TESTS:1=SW,2=OUTS,3=LCD,4=KEYPAD,5=RCPT <

>A=PROKEE, B=COUNT, C=RESET, D=EXIT      <

CNT TEST 1-00000 3-00000 5-00000 7-00000<

>D=EXIT   2-00000 4-00000 6-00000 8-00000<

CNT TEST 1-00000 3-00000 5-00000 7-00000

>D=EXIT   2-00050 4-00000 6-00000 8-00000< (GOOD TEST ON HOSE 2)

ZERO QTY INDICATES A PROBLEM WITH PULSER,CONNECTING CABLE OR POSSIBLY FUELMASTER PEDESTAL I/O BOARD (SEE PAPER CLIP CHECK)